EasyManua.ls Logo

Danfoss iC2 - 7.6.2 Protection (Menu Index 5.2)

Danfoss iC2
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Application Guide | iC2-Micro Frequency Converters
Parameter
number:
1685 Unit:
Data type: uint16 Access type: Read
P 5.1.27 FC Port REF 1
Use this parameter to view the last received reference from the FC port.
Default value: 0 Parameter type: Range (-32768–32767)
Parameter
number:
1686 Unit:
Data type: int16 Access type: Read
7.6.2 Protection (Menu Index 5.2)
P 5.2.1 Warning Reference High
Use this parameter to set the high limit for the reference range. When the actual reference exceeds this limit, warning bit 19 is set in P
5.1.9 Ext. Status Word. The output relay or the digital output can be configured to indicate this warning. The warning indicator light of
the control panel is not turned on when this limit is reached.
Default value: 4999.000 Parameter type: Range (-4999.000–4999.000)
Parameter
number:
455 Unit:
Data type: int32 Access type: Read/Write
P 5.2.2 Warning Reference Low
Use this parameter to set the low limit for the reference range. When the actual reference exceeds this limit, warning bit 20 is set in P
5.1.9 Ext. Status Word. The output relay or the digital output can be configured to indicate this warning. The warning indicator light of
the control panel is not turned on when this limit is reached.
Default value: -4999.000 Parameter type: Range (-4999.000–4999.000)
Parameter
number:
454 Unit:
Data type: int32 Access type: Read/Write
P 5.2.3 Warning Feedback High
Use this parameter to set the high limit for the feedback range. When the feedback exceeds this limit, warning bit 5 is set in P 5.1.9
Ext.Status Word. The output relay or the digital output can be configured to indicate this warning. The warning indicator light of the
control panel is not turned on when this limit is reached.
Default value: 4999.000 Parameter type: Range (-4999.000–4999.000)
Parameter
number:
457 Unit: ProcessCtrlUnit
Data type: int32 Access type: Read/Write
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 | 145

Table of Contents

Related product manuals