Parameter
number:
1695 Unit: –
Data type: uint32 Access type: Read
P 5.1.16 Reference [Unit]
Use this parameter to view the present value of reference applied in the frequency converter resulting from the choice of configuration
in P 5.4.2 Operation Mode.
Default value: 0.000 Parameter type: Range (-4999.000–4999.000)
Parameter
number:
1601 Unit: ReferenceFeedbackUnit
Data type: int32 Access type: Read
P 5.1.17 Reference [%]
Use this parameter to view the total reference.
Default value: 0.0 Parameter type: Range (-200.0–200.0)
Parameter
number:
1602 Unit: %
Data type: int16 Access type: Read
P 5.1.18 External Reference
Use this parameter to view the sum of all external reference sources defined in P 5.5.3.7 Reference 1 Source, P 5.5.3.8 Reference 2
Source, and P 5.5.3.9 Reference 3 Source.
Default value: 0.0 Parameter type: Range (-200.0–200.0)
Parameter
number:
1650 Unit: %
Data type: int16 Access type: Read
P 5.1.19 Main Actual Value [%]
Use this parameter to view the Main Actual Value sent from the frequency converter via bus.
Default value: 0.00 Parameter type: Range (-200.00–200.00)
Parameter
number:
1605 Unit: %
Data type: int16 Access type: Read
P 5.1.26 FC Port CTW 1
Use this parameter to view the 2 byte control word (CTW) received from the bus master.
Default value: 1084 Parameter type: Range (0–65535)
144 | Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters