Application Guide | iC2-Micro Frequency Converters
7.10 Connectivity (Menu Index 10)
7.10.1 FC Port Settings (Menu Index 10.1)
P 10.1.1 Protocol
Select the protocol for the integrated RS485 port.
Default value: 0 [FC] Parameter type: Selection
Parameter
number:
830 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name Selection description
0 FC Communication according to the FC protocol.
2 Modbus RTU Communication according to the Modbus RTU protocol.
P 10.1.2 Address
Enter the address for the RS485 port. Valid range: 1-126 for FC-bus or 1-247 for Modbus.
Default value: 1 Parameter type: (0–247)
Parameter
number:
831 Unit: –
Data type: uint8 Access type: Read/Write
P 10.1.3 Baud Rate
Select the baud rate for the RS485 port..
Default value: 2 [9600] Parameter type: Selection
Parameter
number:
832 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name
0 2400 Baud
1 4800 Baud
2 9600 Baud
3 19200 Baud
4 38400 Baud
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 | 257