Selection number Selection name
5 57600 Baud
6 76800 Baud
7 115200 Baud
P 10.1.4 Parity/Stop Bits
Parity and stop bits for the protocol using the FC port. For some of the protocols, not all options are available.
Default value: 0 [Even Parity, 1 Stop Bit] Parameter type: Selection
Parameter
number:
833 Unit:
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name
0 Even Parity, 1 Stop Bit
1 Odd Parity, 1 Stop Bit
2 No Parity, 1 Stop Bit
3 No Parity, 2 Stop Bits
P 10.1.5 Maximum Response Delay
Specify the maximum allowed delay time between receiving a request and transmitting the response. If this time is exceeded, no
response will be returned.
Default value: Size Related Parameter type: Range (0.100–10.000)
Parameter
number:
836 Unit: s
Data type: uint16 Access type: Read/Write
P 10.1.6 Minimum Response Delay
Specify the minimum delay time between receiving a request and transmitting a response. This is used for overcoming modem
turnaround delays.
Default value: 0.010 Parameter type: Range (1–500)
Parameter
number:
835 Unit: s
Data type: uint16 Access type: Read/Write
258 | Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters