Default value: 0 Parameter type: Selection
Parameter
number:
1303 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name Selection description
0 Do not reset SLC Do not reset SLC.
1 Reset SLC Reset all SLC parameters to default settings.
7.8.2.4 Comparators (Menu Index 8.4.3)
Comparators are used for comparing continuous variables (output frequency, output current, analog input, and so on) to fixed preset
values.
Comparator Operator
=
TRUE longer than.
Comparator Operand
P 8.4.3.3
Comparator Value
e30bv191.10
Figure 79: Comparator Parameters
In addition, there are digital values which are compared to fixed time values. See explanation in P 8.4.3.1 Comparator Operand.
Comparators are evaluated once in each scan interval. Use the result (TRUE or FALSE) directly. All parameters in this parameter group are
array parameters with index 0–5. Select index 0 to program Comparator 0, select index 1 to program Comparator 1, and so on.
P 8.4.3.1 Comparator Operand
Select the variable to be monitored by the comparator. This is an array parameter containing comparators 0–5.
Default value: 1 Parameter type: Selection
Parameter
number:
1310 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name Selection description
0 Disabled Comparator is disabled.
1 Reference Resulting remote reference (not local) as a percentage.
2 Feedback Feedback in [Hz].
3 Motor speed Motor speed in [Hz].