EasyManua.ls Logo

Danfoss iC2 - Page 171

Danfoss iC2
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Application Guide | iC2-Micro Frequency Converters
P 5.7.4 DC Brake Current %
Use this parameter to enter a value for current as a percentage of the rated motor current. See P 4.2.2.3 Nominal Current. When the
speed is lower than the limit set in P 5.7.5 DC Brake Frequency, or when the DC-brake Inverse function is active, (in parameter group
9.4.1. Digital Inputs set to [5] DC-brake Inverse; or via the serial port), a DC-brake current is applied on a stop command. See P 5.7.3 DC
Brake Time for duration.
Default value: 50 Parameter type: Range (0–150)
Parameter
number:
201 Unit: %
Data type: uint16 Access type: Read/Write
NOTICE
MOTOR OVERHEATING
The maximum value depends on the rated motor current. To avoid motor damage caused by overheating, do not run at 100% for
too long.
P 5.7.5 DC Brake Frequency
Use this parameter to set the DC-brake cut in speed for activation of the DC-brake current set in P 5.7.4 DC Brake Current, together with a
stop command.
Default value: 0.0 Parameter type: Range (Size Related)
Parameter
number:
204 Unit: Hz
Data type: uint16 Access type: Read/Write
P 5.7.6 DC Hold Current %
Use this parameter to set the holding current as a percentage of the rated motor current, see P 4.2.2.3 Nominal Current). The parameter
holds the motor function (holding torque) or preheats the motor. This parameter is active if DC hold is selected in P 5.6.2 Start Function
as [0] DC Hold/Delay Time or P 5.7.1 Function at Stop as [1] DC Hold / Motor Preheat.
Default value: 50 Parameter type: Range (0–160)
Parameter
number:
200 Unit: %
Data type: uint16 Access type: Read/Write
NOTICE
The maximum value depends on the rated motor current. Avoid 100% current for too long. It may damage the motor.
P 5.7.7 Quick Stop Ramp Time
Use this parameter to enter the quick-stop ramp-down time, which is the deceleration time from the nominal motor speed to 0 Hz.
Ensure that no resulting overvoltage occurs in the inverter due to regenerative operation of the motor required to achieve the given
ramp-down time. Ensure also that the generated current required to achieve the given ramp-down time does not exceed the current
limit (set in P 2.7.1 Current Limit). Activate quick stop with a signal on a selected digital input, or via the serial communication port.
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 | 171

Table of Contents

Related product manuals