Application Guide | iC2-Micro Frequency Converters
Selection number Selection name
106 Power
107 Speed
113 PID Clamped Output
139 Bus Control
254 DC Link Voltage
P 9.5.1.3 T31 Output Max Scale
Scale for the maximum output (20 mA) of the analog signal at terminal 31. Set the value to be the percentage of the full range of the
variable selected in P 9.5.1.2 Terminal 31 Analog Output.
Default value: 100.00 Parameter type: Range (0.00–200.00)
Parameter
Number
694 Unit: %
Data type: uint16 Access type: Read/Write
P 9.5.13
T31 Output
Max Scale
Variable for
Output
example: Power
Figure 85: Output Scale versus Current
P 9.5.1.4 T31 Output Min Scale
Scale for the maximum output (20 mA) of the analog signal at terminal 31. Set the value to be the percentage of the full range of the
variable selected in P 9.5.1.2 Terminal 31 Analog Output.
Default value: 0 Parameter type: Range (0.00–200.00)
Parameter
Number
693 Unit: %
Data type: uint16 Access type: Read/Write
P 9.5.1.5 T31 Output Bus Control
Holds the analog level of Output 31 if controlled by bus.
Default value: 0 Parameter type: Range (0–16384)
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 | 249