EasyManuals Logo

Danfoss VLT AQUA Drive FC 202 Design Guide

Danfoss VLT AQUA Drive FC 202
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #90 background imageLoading...
Page #90 background image
3.8.9.3 Adjustable Frequency Drive with
Modbus RTU
The adjustable frequency drive communicates in Modbus
RTU format over the built-in RS485 interface. Modbus RTU
provides access to the control word and bus reference of
the adjustable frequency drive.
The control word allows the Modbus master to control
several important functions of the adjustable frequency
drive:
Start
Stop of the adjustable frequency drive in various
ways:
-
Coast stop
-
Quick stop
-
DC brake stop
-
Normal (ramp) stop
Reset after a fault trip
Run at a variety of preset speeds
Run in reverse
Change the active set-up
Control the adjustable frequency drive’s built-in
relay
The bus reference is commonly used for speed control. It is
also possible to access the parameters, read their values,
and, where possible, write values to them. This permits a
range of control options, including controlling the setpoint
of the adjustable frequency drive when its internal PI
controller is used.
3.8.9.4
Network Conguration
To enable Modbus RTU on the adjustable frequency drive,
set the following parameters:
Parameter Setting
8-30 Protocol Modbus RTU
8-31 Address 1-247
8-32 Baud Rate 2400-115200
8-33 Parity / Stop Bits Even parity, 1 stop bit (default)
Table 3.33 Modbus RTU Parameters
3.8.10
Modbus RTU Message Framing
Structure
3.8.10.1 Adjustable Frequency Drive with
Modbus RTU
The controllers are set up to communicate on the Modbus
network using RTU mode, with each byte in a message
containing 2 4-bit hexadecimal characters. The format for
each byte is shown in Table 3.34.
Start
bit
Data byte Stop/
parity
Stop
Table 3.34 Format for Each Byte
Coding system 8–bit binary, hexadecimal 0–9, A–F.
Two hexadecimal characters contained in
each 8-bit eld of the message.
Bits per byte 1 start bit.
8 data bits, least signicant bit sent rst;
1 bit for even/odd parity; no bit for no
parity.
1 stop bit if parity is used; 2 bits if no
parity.
Error check eld Cyclical redundancy check (CRC).
3.8.10.2 Modbus RTU Message Structure
The transmitting device places a Modbus RTU message
into a frame with a known beginning and ending point.
This allows receiving devices to begin at the start of the
message, read the address portion, determine which
device is addressed (or all devices, if the message is
broadcast), and to recognize when the message is
completed. Partial messages are detected, and errors are
set as a result. Characters for transmission must be in
hexadecimal 00 to FF format in each eld. The adjustable
frequency drive continuously monitors the network bus,
also during silent intervals. When the rst eld (the address
eld) is received, each adjustable frequency drive or device
decodes it to determine which device is being addressed.
Modbus RTU messages addressed to zero are broadcast
messages. No response is permitted for broadcast
messages. A typical message frame is shown in Table 3.35.
Start Address Function Data CRC
check
End
T1-T2-T3-
T4
8 bits 8 bits N x 8 bits 16 bits T1-T2-T3-
T4
Table 3.35 Typical Modbus RTU Message Structure
System Integration
VLT
®
AQUA Drive FC 202
88 Danfoss A/S © 09/2014 All rights reserved. MG20N622
33

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals