Depending on the application and the purpose of using it,
this feature can be used as a preventive or reactive
measure and can be triggered/started in the following
ways:
On each start command (29-11 Derag at Start/
Stop)
On each stop command (29-11 Derag at Start/
Stop)
On each start/stop command (29-11 Derag at
Start/Stop)
On digital input (parameter group 5-1* Digital
Inputs)
On drive action with the smart logic controller
(13-52 SL Controller Action)
As timed action (parameter group 23-** Time-
based Functions)
On high power (parameter group 29-2* Derag
Power Tuning)
4.2.4
Pre/post Lube
Certain motors require lubrication of their mechanical parts
before and during running to prevent damage/wear. This is
especially the case when the motor has not been running
for extended periods of time. Pre-lube also supports
applications that may require certain exhaust fans to be
running. The Pre-lube feature signals an external device to
start performing a specic action for a user-dened period
of time beginning at the rising edge of a run command
(for example, start request). Furthermore, a start delay
(1-71 Start Delay) can be entered such that the pre-lube
only occurs while the adjustable frequency drive is
stopped and the pre-lube completes just before the
adjustable frequency drive starts to ramp up. Pre-lube can
also be congured such that the external device remains
signaled at all times when the adjustable frequency drive
is in a running state or such that the signal stays on after
the motor has stopped (29-42 Post Lube Time). Application
examples include a device to lubricate the mechanical
parts of a motor/pump or some type of exhaust fan unit.
An example use case for a lubrication device would be to
start lubrication at the rising edge of a start request. Delay
the start for a period of time and stop lubrication when
the delay expires and the adjustable frequency drive starts.
Figure 4.2 shows a dierent usage of the feature. In this
case, the delay expires while the adjustable frequency
drive is already ramping up. See the related parameters in
Table 4.1.
130BD765.10
N
MAX
N
MIN
0
1
1
0
0
1
2
3
t1 t3t2
T
T
T
1
Speed curve
2 Start command (for example, terminal 18)
3 Pre lube output signal
t
1
Start command issued (for example, terminal 18 is set
active). The start delay timer (1-71 Start Delay) and the
pre lube timer (29-41 Pre Lube Time).
t
2
The start delay timer expires. The adjustable frequency
drive starts to ramp up.
t
3
The pre-lube timer (29-41 Pre Lube Time) expires.
Figure 4.2 Pre/post Lube Function Example
Parameter and
Name
Description Settings Unit
29-40 Pre/Post
Lube Function
Select the pre/post
lube function. Use
1-71 Start Delay to
set the delay before
the motor will start
ramping.
[0]*Disabled
[1] Pre-lube only
[2] Pre & running
[3] Pre & running
& post
-
29-41 Pre Lube
Time
Enter the duration of
the signal after the
start signal. Used
only when [1] Pre
lube Only is selected
in 29-40 Pre/Post Lube
Function.
0-600 (*10) s
29-42 Post Lube
Time
Select the duration of
the signal after the
motor has stopped.
Used only when [3]
Pre & running & post
is selected in
29-40 Pre/Post Lube
Function.
0-600 (*10) s
Table 4.1 Pre/Post Lube Parameters
Application Examples
VLT
®
AQUA Drive FC 202
102 Danfoss A/S © 09/2014 All rights reserved. MG20N622
44

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals