1-71 Start Delay.
T
1-79
1-79 Pump Start Max Time to Trip. This time includes
the time in T
1-71
.
N
1-86
1-86 Trip Speed Low [RPM]. If the speed drops below
this value during normal operation, the adjustable
frequency drive trips.
1 Normal operation.
Figure 4.4 Advanced Minimum Speed Monitoring
4.3 Application Set-up Examples
The examples in this section are intended as a quick reference for common applications.
Parameter settings are the regional default values unless otherwise indicated (selected in 0-03 Regional Settings).
Parameters associated with the terminals and their settings are shown next to the drawings.
Required switch settings for analog terminals A53 or A54 are also shown.
NOTICE!
When the optional STO feature is used, a jumper wire may be required between terminal 12 (or 13) and terminal 37 for
the adjustable frequency drive to operate when using factory default programming values.
SLC Application Example
One sequence 1:
1. Start.
2. Ramp-up.
3. Run at reference speed 2 s.
4. Ramp-down.
5. Hold shaft until stop.
Application Examples
VLT
®
AQUA Drive FC 202
104 Danfoss A/S © 09/2014 All rights reserved. MG20N622
44

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals