V0913, 10.53
When the cursor is placed on Diagnostic mode an additional function will appear. Tapping
Create .dat-file will store the most important product and control data on the connected USB
key. This information can be helpful for the maintenance support.
Replace module
An axis module can easily be exchanged without special access following the exchange
procedure. Only when applicable, this function will be available.
The module exchange procedure is as follows:
1 Switch off the DA-control and disconnect the DM-module that needs to be
replaced.
2 Connect the new DM-module of the same type and switch on the machine.
3 An error message with the ID of the original module will appear on the screen.
4 Select the Machine mode and go to the Maintenance tab.
5 Tap Install Module.
6 A Window appears asking to replace the module with the new one. Tap Yes to
accept.
7 The control will reboot to initialize the new module. If necessary the software of the
new module will be updated automatically.