BACnet MS/TP Communication Data Bus Fundamentals
122 ECLYPSE User Guide
Using Repeaters to Extend the Data Bus
A BACnet MS/TP data bus segment can be up to 1220 meters (4000 feet) long with up to a
maximum of 50 devices. When a greater length is required, a solution is to use a repeater. A
repeater increases the maximum length of the data bus.
Using a Repeater to Extend the Length of the BACnet MS/TP Data Bus
Repeaters can be used to extend a BACnet MS/TP data bus up to 3660 meters maximum
total length. Do not use more than two repeaters on a BACnet MS/TP LAN.
A BACnet MS/TP repeater is a bi-directional device that regenerates and strengthens the
electrical signals that pass through it. It creates two electrically-isolated BACnet MS/TP data
bus segments that transparently enable devices on one side of the repeater to communicate
with any device on the other side. The two BACnet MS/TP data bus segments have the
same requirements of an ordinary BACnet MS/TP data bus segment; that is, each BACnet
MS/TP data bus segment:
Can be up to 1220 meters (4000 feet) long.
The first and last device on the data bus must have End-of-Line (EOL) termination
resistors connected across the two data lines/wires of the twisted pair.
Must respect the maximum limit for Device Loading on page 113.
Will have the same network number as they remain part of the same network or LAN.
Distech Controls recommends that you connect no more than 50 of our ⅛ or ½-load devices
on all BACnet MS/TP Data Bus repeater segments when a baud rate of 19 200 or higher is
used (preferably 38 400 baud). This is to ensure that the BACnet MS/TP Data Bus has
enough bandwidth to efficiently communicate network variables between controllers.
Do not use more than two repeaters on a BACnet MS/TP data bus.
A repeater can only connect two BACnet MS/TP data bus segments even if it has
ports to support more than two BACnet MS/TP data bus segments.
A repeater can be added anywhere to a data bus segment including the end of the segment
as shown below.
MS/TP Data Bus:
- 3660 m (12 000 ft) Maximum Total
- 50 Connected Devices Maximum Total
MS/TP Data Bus Segment:
- 1220 m (4 000 ft) Maximum
MS/TP Data Bus Segment:
- 1220 m (4 000 ft) Maximum
MS/TP Data Bus Segment:
- 1220 m (4 000 ft) Maximum
< 7.6 m
< 25 ft
MS/TP
Repeater
EOL Terminators
MS/TP
Repeater
EOL Internally Set EOL Internally Set
< 7.6 m
< 25 ft
EOL
ON
EOL
ON
EOL
ON
EOL Internally Set
ECY-S1000
EOL Internally Set
EOL
ON
Figure 11-12: Using a Repeater to Extend the Range of the LAN