BACnet MS/TP Communication Data Bus Fundamentals
124 ECLYPSE User Guide
See When to Use EOL Terminations on page 116 for more information. The shield of one
data bus must be grounded at one point as specified in Data Bus Shield Grounding
Requirements on page 119. The shields of the two data buses must be connected together
and isolated with electrical tape as shown in Figure 11-14. Refer to the controller’s Hardware
Installation Guide for how to identify and set a controller’s built-in EOL terminations.