4 Wiring with
4.3 Function Relays
80 Operating instructions 05/10 MN05013003Z-EN www.eaton.com
▶ Press the OK button.
▶ Press the
í button.
▶ Use the
Í Ú ú í buttons to enter the value 01.000.
▶ Confirm with OK.
The time setpoint
I1 for the pause time is 1 s
▶ Use the
Ú button to enter the value of the second setpoint value I2.
▶ Set this value to 0.5 s.
This is the time value for the pulse time.
▶ Press ESC to leave the parameter entry.
The values are now stored.
▶ Complete the circuit diagram.
▶ Press the ESC button.
▶ Press OK to store the circuit diagram.
▶ Test the circuit diagram with the power flow display.
▶ Switch easy to RUN mode and return to the circuit diagram.
Each parameter set can be displayed using the power flow display for the
circuit diagram.
▶ Move the cursor onto
C1 and press OK.
The parameter set for the counter is displayed with actual and setpoint
values.
▶ Switch I5. The actual value changes.
This is represented in the easy parameter display. In the last line C: 0007
the counter actual value is = 7.
If the actual value is greater than or equal to the setpoint (10), the left
character on the bottom row will change to
â. The contact of counter C1
switches.
The counter contact triggers the timing relay. This causes the warning light
to flash at output Q1.
T1 Ü S +
I1 01,000
I2 00.50
T:
I5-------CC1
I6-------RC1
C1-------TT1
T1-------ÄQ1