• Menu 6-5 Alarm priorities
ALARMPRIOS POS: XXXXX Input Default
KühlstellenprioX Priority of the
alarms can be set
globally using the
refrigeration point
priority (menu
6-1) (Y)
, , (Y,N)
N
Priorität:XX Display of
refrigeration point
priority (menu
6-1)
only displayed if
Kühlstellenprio is
set to Y
The following parameters are only displayed if
Kuhlstellenprio is set to N. The possible entries for the
priority of the alarms have the following meanings: -=Event
is ignored 0=Message (only entry in message list) 1=Alarm
with priority 1 .. 99=Alarm with priority 99
Low temp. Lower alarm
temperature limit
value undercut;
priority is
applicable for all
messages low-
temp. zone 1,
low-temp. zone 2
-, 0..99 2
High temp Upper alarm
temperature limit
value exceeded;
priority is
applicable for all
messages high-
temp. zone 1,
high-temp. zone
2
-, 0..99 1
Sensor fault Temperature
sensor failed
-, 0..99 2
No Defrost No defrost within
the alarm delay
time
Priority is
applicable for the
message No
Defrost
-, 0..99 2
Timer-Term. Defrost Defrost ended by
safe defrost time
-, 0..99 0
Power failure Start-up after
power failure
-, 0..99 0
First start Commissioning of
the controller
(basic settings
loaded!)
-, 0..99 2