Firmware V3.15
21.04.2021
164/401
The value is selected in accordance with the entry. The check mark indicates the current setting.
FÜHLERTYP POS: XXXXX Input Default
L243
Temperaturerange-50..50°C
K277 Temperaturerange-50..50°C
5K3A1 Temperature range 0..100°C
Menu 6-3 Cooling
KÜHLUNG POS: XXXXX Input Default
min. Laufzeit XX K Minimum run time of the cooling 0..15 2 m
min. Standzeit XX m Minimum switch-off time of the cooling 0..15 2 m
Dauerl.überw. XX m Time for the forced interruption of the cooling during
continuous operation
--, 0..15 0 m
Notbetrieb XX m If necessary sensors for the regulation fail, the
solenoid valve is actuated with the opening degree in
[%]set here.
0..100 40%
Menu 6-4 - Language
SPRACHE POS: XXXXX Input Default
Deutsch D
English GB
Français F
Espagnol E
Finnish FIN
Türkce TR
Cesky CZ