Menu2-2-1Zone1
DEFROST 1 POS: XXXXX Entry Default
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 5..20 8 °C
M/S Degiv.Fct. XXX Configuration of the defrost via CAN bus function.
For details see chapter Master-Slave-Modus -
Abtau-Synchronisation über CAN-Bus.
OFF, MASTR, SLAVE OFF
M/S CAN Adr. XXX Selection of the controller (1..99) participating in
the defrost via CAN bus which is the master.
"--", if this controller is itself master(Parameter M/
S Degiv.Fct.. = MASTR)
---, 1..99
DS-Function XXX Configuration of the defrost sequence function
(DS).For details see chapter Folgeabtauung (FA)
über CAN-Bus.
OFF, MASTR, SLAVE OFF
DS-Group XXX Selection of which group a defrost sequence of
this controller (1..99) belongs to.
---, 1..99
DS-Master XXX Selection of which controller (1..99) participating
in the defrost sequence is the master.
"--", if this controller is itself the master(Parameter
DS-Function = MASTR)
---, 1..99
DS-Wait time XXXm Wait time for the defrost sequence 0..127 1 min
Menu 2-2-2 Zone 2
Not used with this controller type.
Menu2-2-3Zone1AAltern.
DEFROST 1A POS: XXXXX Entry Default
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 5..20 5 °C
Menu 2-3
Not used with this controller type.
Menu2-4Alarm
ALARM POS: XXXXX
1 Zone 1 Menu 2-4-1
2 Not used with this controller type
3 Zone 1A Altern. Menu 2-4-3
Not shown when setpoint toggle is disabled (Menu 3-3)
Menu2-4-1Zone1
ALARM 1 POS: XXXXX Entry Default
High Temp Setp XX °C High temperature setpoint at which High
Temperature alarm is generated
0..30 8 °C
Low Temp Setp. XX K Low temperature setpoint (difference below
temperature control setpoint) at which Low
Temperature alarm is generated
--, 0..6 4 K