• Menu6-5Alarmpriorities
ALARMPRIOS POS: XXXXX Entry Default
Prio.Refrig. Pt. X Global alarm priority by refrigeration point
priority (Menu 6-1) (Y)
, ,(Y,N)
N
Priority: XX Show refrigeration point priority (Menu 6-1)
Only shown when refrigeration point priority
set to Y.
Following parameters are only shown when
refrigeration point priority is set to N. Meaning of
usable entries for alarm priority:-=Event ignored
0=Message (entered only in message log)
1=Priority 1 alarm..99=Priority 99 alarm
Low Temp. Temperature below lower alarm limit
Priority applies to following alarms:
Low Temp. Zone1, Low Temp. Zone2
-, 0..99 2
High Temp. Temperature above upper alarm limit
Priority applies to following alarms:
High Temp. Zone1, High Temp. Zone2
-, 0..99 1
Sensor Fault Temperature sensor failure -, 0..99 2
No Defrost No defrost within alarm delay interval
Priority applies to following alarm: No
defrost
-, 0..99 2
Timer-Term.Defr. Defrosting terminated by safe defrost time -, 0..99 0
Power Failure Start following power failure -, 0..99 0
First Start Controller start up (basic settings loaded!) -, 0..99 2
Manual Shutoff Manual switch Input D31/D32 set OFF -, 0..99 0
Hardware Fault Internal hardware fault
Priority applies to following alarms:
EEPROM Fault, RTC Fault, Flash Fault
-, 0..99 1
Setpoint Change Message generated on changing setpoint 0..99 0
Refrig.Pt.Dis. Cooling by pack controller via CAN bus
interrupted
-, 0..99 0
Battery Voltage Battery low -, 0..99 0