Menu2-1-3Zone1AAltern.
COOLING 1A POS: XXXXX Entry Default
Setpoint R4.1 XXX °C Room air temperature setpoint -10..30 3 °C
Hystersis R4.1 X K Room air temperature hysteresis setpoint 1..8 1 K
HT. Cir. Setp. XXX °C Heating circuit setpoint, only shown when single-
zone operation is set (Menu 6-1)
--, -10..30 3 °C
HT. Cir. Hyst. X K Heating circuit hysteresis, only shown when single-
zone operation is set (Menu 6-1)
1..8 1 K
Menu2-1-4Zone2AAltern.
COOLING 2A POS: XXXXX Entry Default
Setpoint R4.3 XXX °C Room air temperature setpoint -10..30 3 °C
Hystersis R4.3 X K Room air temperature hysteresis setpoint 1..8 1 K
Menu2-2Defrost
DEFROST POS: XXXXX
1 Zone 1 Menu 2-2-1
2 Zone 2 Menu 2-2-2
Only shown when two-zone operation is set (Menu 6-1)
3 Zone 1A Altern. Menu 2-2-3
Not shown when setpoint toggle is disabled (Menu 3-3)
4 Zone 2A Altern. Menu 2-2-4
Only shown when two-zone operation is set (Menu 6-1) and setpoint toggle is not
disabled (Menu 3-3)