Menu2-2-1Zone1
DEFROST 1 POS: XXXXX Entry Default
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 0..30 5 °C
Wait Time xx m Waiting time setpoint between cooling and
defrosting
0 .. 15 0 m
Drip Time x m Waiting time (drain time) setpoint between
defrosting and cooling
0 .. 15 0 m
2.Defrst Level xx °C Setpoint 2nd defrost stage --, -20..30 –°C
M/S Degiv.Fct. XXX Configuration of the defrost via CAN bus function.
For details see chapter Master-Slave-Modus -
Abtau-Synchronisation über CAN-Bus.
OFF, MASTR, SLAVE OFF
M/S CAN Adr. XXX Selection of the controller (1..99) participating in
the defrost via CAN bus which is the master.
"--", if this controller is itself master(Parameter M/
S Degiv.Fct.. = MASTR)
---, 1..99 –
DS-Function XXX Configuration of the defrost sequence function
(DS).For details see chapter Folgeabtauung (FA)
über CAN-Bus.
OFF, MASTR, SLAVE OFF
DS-Group XXX Selection of which group a defrost sequence of
this controller (1..99) belongs to.
---, 1..99 –
DS-Master XXX Selection of which controller (1..99) participating
in the defrost sequence is the master.
"--", if this controller is itself the master (Parameter
DS-Function = MASTR)
---, 1..99 –
DS-Wait time XXXm Wait time for the defrost sequence 0..127 1 min
Menu2-2-2Zone2
DEFROST 2 POS: XXXXX Entry Default
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 0..30 5 °C
Wait Time xx m Waiting time setpoint between cooling and
defrosting
0 .. 15 0 m
Drip Time x m Waiting time (drain time) setpoint between
defrosting and cooling
0 .. 15 0 m