Menu2-4-1Zone1
ALARM 1 POS: XXXXX Entry Default
High Temp Setp XX °C High temperature setpoint at which High
Temperature alarm is generated
-30..30 -12 °C
Low Temp Setp. XX K Low temperature setpoint (difference below
temperature control setpoint) at which Low
Temperature alarm is generated
--, 0..6 2 K
Menu2-4-2Zone2
ALARM 2 POS: XXXXX Entry Default
High Temp Setp XX °C High temperature setpoint at which High
Temperature alarm is generated
-30..30 -12 °C
Low Temp Setp. XX K Low temperature setpoint (difference below
temperature control setpoint) at which Low
Temperature alarm is generated
--, 0..6 2 K