6.Selectmenu6 Configuration – 3 Cooling.
6 Configuration - 3 Cooling
KÜHLUNGPOS: XXX
Korroff. to XXK Correction offset which is applied to the t 0 actual value received from the pack
controller via CAN bus. This enables pressure losses in the refrigerant line to be
compensated.Ifthisvalueissetto"–",thecasecontrollerregulatesusingthe
temperature sensors at the evaporator input and output (standalone operation).
Dauerl.Überw. XXm Continuous use monitoring
DG-Betrieb AUS This must be set for UA 131 E to guarantee that the D2D defrost runs correctly. The
defrost timer should be set to EXT when activating this operating mode.
Lüfterverzöger XX°C Maximum value at the defrost sensor, at which the fan should be switched on after a
delay (e.g. after the defrost)
7. Exit the Configuration menu by tapping the ESC button twice and select 3 Clock – 2 Defrost timer
Input of the relevant parameters in the following screen.
3 Clock - 2 Defrost Timer
ABTAUUHRPOS: XXX
AbtauuhrINT Selection of defrost using external or internal defrost timer
Sicherheitsz.60m Safe defrost time; the defrost is not longer than this time.
Defrost 1 DD-DD hh:mm Entry of defrost times
Defrost 2 DD-DD hh:mm
...
Defrost 14 DD-DD hh:mm
man. AbtauungAUS Manual defrost ON/OFF
8. Exit from the 2 Defrost Timer menu by tapping the ESC button.
9. Select menu 3 Toggle Setpoint, input of the relevant parameters in the following screen:
3 Clock - 3 Toggle Setpoint
UMSCHALTNGPOS: XXX
StatusAUS Only visible if Sollumschaltg. is set to INT or EXT
Sollumschaltg.EXT Selection INT, EXT, --: internal, external, deactivated toggle setpoint
Selection
INT: internal
EXT: external
--: deactivated toggle setpoint
Laufzeit Rollo0s Input operating time of the blind of the multidecks
Um EIN: DD-DD hh:mm Input time for toggle setpoint
(only visible if Sollumschaltg. is set to INT)