Commissioning Promag 53 PROFIBUS DP/PA
108 Endress+Hauser
Possible settings
Factory setting
SETTOT_TOTAL module
The module combination SETTOT_TOTAL (slots 2 to 4) consists of the functions SETTOT
and TOTAL.
With this module combination:
• The totalizer can be controlled via the automation system (SETTOT).
• The totalizer value, is transmitted, including the status (TOTAL)
SETTOT function
In the SETTOT function, the totalizer can be controlled via control variables.
The following control variables are supported:
• 0 = Totalize (factory setting)
• 1 = Reset totalizer (the totalizer value is reset to 0)
• 2 = Accept totalizer preset
!
Note!
After the totalizer value has been reset to 0 or set to the preset value, the totalizing
continues automatically. The control variable does not have to be changed to 0 again to
restart totalizing.
Stopping totalizing is controlled in the SETTOT_MODETOT_TOTAL module via the
MODETOT function. → 109
TOTAL function
For a description of the TOTAL function, refer to TOTAL module → 107
Data structure of the SETTOT_TOTAL module combination
SETTOT_MODETOT_TOTAL module
The module combination SETTOT_MODETOT_TOTAL (slots 2 to 4) consists of the functions
SETTOT, MODETOT and TOTAL.
With this module combination:
• The totalizer can be controlled via the automation system (SETTOT).
• The totalizer can be configured via the automation system (MODETOT).
• The totalizer value, is transmitted, including the status (TOTAL)
Totalizer value/measured variable ID for CHANNEL function
VOLUME FLOW 273
MASS FLOW 277
OFF 0
Module Totalizer
function block
Totalizer value/
Measured variable
Unit ID for CHANNEL
function
TOTAL (slot 2) 1 VOLUME FLOW m
273
TOTAL (slot 3) 2 VOLUME FLOW m
273
TOTAL (slot 4) 3 VOLUME FLOW m
273
Output data Input data
SETTOT TOTAL
Byte 1 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5
Control Totalizer value (IEEE 754 floating point number) Status