Commissioning Promag 53 PROFIBUS DP/PA
108 Endress+Hauser
Possible settings
Factory setting
SETTOT_TOTAL module
The module combination SETTOT_TOTAL (slots 2 to 4) consists of the functions SETTOT
and TOTAL.
With this module combination:
The totalizer can be controlled via the automation system (SETTOT).
The totalizer value, is transmitted, including the status (TOTAL)
SETTOT function
In the SETTOT function, the totalizer can be controlled via control variables.
The following control variables are supported:
0 = Totalize (factory setting)
1 = Reset totalizer (the totalizer value is reset to 0)
2 = Accept totalizer preset
!
Note!
After the totalizer value has been reset to 0 or set to the preset value, the totalizing
continues automatically. The control variable does not have to be changed to 0 again to
restart totalizing.
Stopping totalizing is controlled in the SETTOT_MODETOT_TOTAL module via the
MODETOT function. 109
TOTAL function
For a description of the TOTAL function, refer to TOTAL module 107
Data structure of the SETTOT_TOTAL module combination
SETTOT_MODETOT_TOTAL module
The module combination SETTOT_MODETOT_TOTAL (slots 2 to 4) consists of the functions
SETTOT, MODETOT and TOTAL.
With this module combination:
The totalizer can be controlled via the automation system (SETTOT).
The totalizer can be configured via the automation system (MODETOT).
The totalizer value, is transmitted, including the status (TOTAL)
Totalizer value/measured variable ID for CHANNEL function
VOLUME FLOW 273
MASS FLOW 277
OFF 0
Module Totalizer
function block
Totalizer value/
Measured variable
Unit ID for CHANNEL
function
TOTAL (slot 2) 1 VOLUME FLOW m
273
TOTAL (slot 3) 2 VOLUME FLOW m
273
TOTAL (slot 4) 3 VOLUME FLOW m
273
Output data Input data
SETTOT TOTAL
Byte 1 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5
Control Totalizer value (IEEE 754 floating point number) Status