EasyManua.ls Logo

Endress+Hauser PROline promag 53 - Storage

Endress+Hauser PROline promag 53
190 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Promag 53 PROFIBUS DP/PA Installation
Endress+Hauser 11
Transporting flanged devices DN 300 (12")
Use only the metal eyes on the flanges for transporting the device, lifting it and positioning
the sensor in the piping.
"
Caution!
Do not attempt to lift the sensor with the tines of a fork-lift truck beneath the metal casing.
This would buckle the casing and damage the internal magnetic coils.
a0004295
Fig. 5: Transporting sensors with DN > 300 (12")
3.1.3 Storage
Note the following points:
Pack the measuring device in such a way as to protect it reliably against impact for storage
(and transportation). The original packaging provides optimum protection.
The storage temperature corresponds to the operating temperature range of the
measuring transmitter and the appropriate measuring sensors 160.
The measuring device must be protected against direct sunlight during storage in order to
avoid unacceptably high surface temperatures.
Choose a storage location where moisture does not collect in the measuring device. This
will help prevent fungus and bacteria infestation which can damage the lining.
Do not remove the protection plates or caps on the process connections until you are ready
to install the device. This is particularly important in the case of sensors with PTFE linings.

Table of Contents

Other manuals for Endress+Hauser PROline promag 53

Related product manuals