Promag 53 PROFIBUS DP/PA Wiring
Endress+Hauser 53
Cable termination in remote version
Promag H
Terminate the signal and coil current cables as shown in the figure below (Detail A).
Fit the fine-wire cores with wire end ferrules (detail B:
m
= ferrules red, Ø 1.0 mm;
n
= ferrule white, Ø 0.5 mm)
"
Caution!
When fitting the connectors, pay attention to the following points:
Signal cable Make sure that the wire end ferrules do not touch the wire shields on the sensor side!
Minimum distance = 1 mm (exception "GND" = green cable)
Coil current cable Insulate one core of the three-core wire at the level of the core reinforcement; you only require two cores for the connection.
On the sensor side, reverse both cable shields approx. 15 mm over the outer jacket. The strain relief ensures an electrical connection with the
connection housing.
TRANSMITTER
Signal cable Coil current cable
A0002686
A0002684
SENSOR
Signal cable Coil current cable
A0002647
A0002648
A
B
GND
m
m
m
m
n
n
n
n
80 (3.15)
50 (1.97)
17 (0.67)
8 (0.31)
mm (inch)
A
B
m
m
m
70 (2.76)
50 (1.97)
8 (0.31)
mm (inch)
10 (0.39)
A
B
GND
m
n
n
n
mm (inch)
80 (3.15)
15 (0.59)
8 (0.31)
17 (0.67)
1 (0.04)
A
B
m
m
70 (2.76)
15 ()0.59
8 (0.31)
40 (1.57)
mm (inch)