Commissioning Promag 53 PROFIBUS DP/PA
90 Endress+Hauser
6.3.3 Quick Setup "Batching"
!
Note!
This function is only available when the additional "batching" software is installed in the
measuring device (order option). You can order this software from Endress+Hauser as an
accessory at a later date. → 128
This Quick Setup menu guides you systematically through the setup procedure for all the
device functions that have to be modified and configured for batching operation. These basic
settings allow simple (one-step) batching processes.
Additional settings, e.g. for multistage batching procedures, must be made via the function
matrix itself (see the "Description of Device Functions" manual).
"
Caution!
The "Batching" Quick Setup sets certain device parameters for discontinuous measurement
operation.
If the measuring device is used for continuous flow measurement at a later time, we
recommend at you rerun the "Commissioning" and/or "Pulsating flow" Quick Setup.
!
Note!
• Before carrying out the Quick Setup "Batching" the Quick Setup "Commissioning" has to be
executed. → 85
• You can find detailed information on the batching functions in the separate "Description of
Device Functions" manual.
• You can also directly control filling process using the local display. During Quick Setup, an
appropriate dialog appears concerning the automatic display configuration. Acknowledge
this by clicking "YES".
This assigns special batching functions (START, PRESET, etc.) to the bottom line of the
display. These can be directly executed on site using the three operating keys (//).
Therefore, the measuring device can be fully deployed in the field as a "batch controller". →
70
• You can also directly control the filling process using the fieldbus.