Promag 53 PROFIBUS DP/PA Operation
Endress+Hauser 81
5.6.5 Relay output configuration
The relay contact can be configured as normally open (NO or make) or normally closed (NC
or break) contacts by means of two jumpers on the pluggable submodule. This configuration
can be called up at any time with the ACTUAL STATUS RELAY function (4740).
#
Warning!
Risk of electric shock. Exposed components carry dangerous voltages. Make sure that the
power supply is switched off before you remove the cover of the electronics compartment.
1. Switch off power supply.
2. Remove the I/O board. 148
3. Position the jumpers (see Figure).
"
Caution!
If you change the setting, you must always change the positions of both jumpers!
Note precisely the specified positions of the jumpers.
4. Installation of the I/O board is the reverse of the removal procedure.
a0004412
Fig. 52: Configuring relay contacts (NC/NO) on the convertible I/O board (submodule) with the help of jumpers.
1 Configured as NO contact (factory setting, relay 1)
2 Configured as NC contact (factory setting, relay 2)
INPUT/OUTPUT 4
INPUT/OUTPUT 3
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
2
3
4
W
E
N
O
1
+
+
2

Table of Contents

Other manuals for Endress+Hauser PROline promag 53

Related product manuals