Promag 53 PROFIBUS DP/PA Commissioning
Endress+Hauser 95
6.3.5 Data backup/transmission
Using the T-DAT SAVE/LOAD function, you can transfer data (device parameters and
settings) between the T-DAT (exchangeable memory) and the EEPROM (device storage
unit).
This is required in the following instances:
• Creating a backup: current data are transferred from an EEPROM to the T-DAT.
• Replacing a transmitter: current data are copied from an EEPROM to the T-DAT and then
transferred to the EEPROM of the new transmitter.
• Duplicating data: current data are copied from an EEPROM to the T-DAT and then
transferred to EEPROMs of identical measuring points.
!
Hinweis!
For information on installing and removing the T-DAT → 146
a0001221-en
Abb. 60: Data backup/transmission with T-DAT SAVE/LOAD function
Information on the LOAD and SAVE options available:
LOAD: Data are transferred from the T-DAT to the EEPROM.
!
Hinweis!
• Any settings already saved on the EEPROM are deleted.
• This option is only available, if the T-DAT contains valid data.
• This option can only be executed if the software version of the T-DAT is the same or newer
than that of the EEPROM. Otherwise, the error message "TRANSM. SW-DAT" appears after
restarting and the LOAD function is then no longer available.
SAVE:
Data are transferred from the EEPROM to the T-DAT.
Esc
E
+
-
XXX.XXX.XX
T-DAT
SAVE/LOAD
Quick Setup
HOME
POSITION
LOAD
YES
NO
CANCELSAVE
YES
NO
Restart of the
measuring device
Input is
saved