Promag 53 PROFIBUS DP/PA Technical data
Endress+Hauser 159
10.1.5 Power supply
Electrical connections
46
Supply voltage
85 to 260 V AC, 45 to 65 Hz
20 to 55 V AC, 45 to 65 Hz
16 to 62 V DC
Cable entries
Power supply and signal cables (inputs/outputs):
Cable entry M20 x 1.5 (8 to 12 mm; 0.31 to 0.47 in)
Sensor cable entry for armored cables M20 x 1.5 (9.5 to 16 mm; 0.37 to 0.63 in)
Threads for cable entries, ½" NPT, G ½"
Connecting cable for remote version:
Cable entry M20 x 1.5 (8 to 12 mm; 0.31 to 0.47 in)
Sensor cable entry for armored cables M20 x 1.5 (9.5 to 16 mm; 0.37 to 0.63 in)
Threads for cable entries, ½" NPT, G ½"
Cable specifications (remote version)
54
Power consumption
AC: <15 VA (including sensor)
DC: <15 W (including sensor)
Switch-on current:
max. 13.5 A (< 50 ms) at 24 V DC
max. 3 A (< 5 ms) at 260 V AC
Power supply failure
Lasting min. 1 power cycle
EEPROM or T-DAT saves measuring system data if power supply fails
S-DAT: exchangeable data storage device which stores the data of the sensor (nominal
diameter, serial number, calibration factor, zero point, etc.)
Potential matching
62
10.1.6 Performance characteristics
Reference operating conditions
To DIN EN 29104 and VDI/VDE 2641:
Fluid temperature: +28 ± 2 °C (+82 ± 4 °F)
Ambient temperature: +22 ± 2 °C (+72 ± 4 °F)
Warm-up period: 30 minutes
Installation:
Inlet run >10 × DN
Outlet run > 5 × DN
Sensor and transmitter grounded.
Sensor centered relative to the pipe.