EasyManua.ls Logo

Endress+Hauser PROline promag 53 - 6.8 PROFIBUS DP;PA Acyclic Data Transmission

Endress+Hauser PROline promag 53
190 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning Promag 53 PROFIBUS DP/PA
122 Endress+Hauser
6.7.4 Configuration examples with Simatic S7 HW-Konfig
Example 1
a00047879
Fig. 65: Complete configuration using the Promag 53 GSD file (complete device functionality)
It is essential to adhere to the following sequence when configuring the modules in the
PROFIBUS master (Class 1):
Slot
sequence
Module
Byte length
input data
Byte length
output data
Description
1AI 5-
Analog Input function block 1
Output variable volume flow (factory setting)
2 SETTOT_MODETOT_TOTAL 5 2
Totalizer function block 1
TOTAL output variable = volume flow (factory setting)
SETTOT totalizer control
MODETOT totalizer configuration
3 SETTOT_MODETOT_TOTAL 5 2
Totalizer function block 2
TOTAL output variable = volume flow (factory setting)
SETTOT totalizer control
MODETOT totalizer configuration
4 SETTOT_MODETOT_TOTAL 5 2
Totalizer function block 3
TOTAL output variable = volume flow (factory setting)
SETTOT totalizer control
MODETOT totalizer configuration
5AI 5-
Analog Input function block 2
Output variable mass flow (factory setting)
6 DISPLAY_VALUE - 5 Value for local display
7 CONTROL_BLOCK - 1 Control of device functions

Table of Contents

Other manuals for Endress+Hauser PROline promag 53

Related product manuals