Commissioning Promag 53 PROFIBUS DP/PA
122 Endress+Hauser
6.7.4 Configuration examples with Simatic S7 HW-Konfig
Example 1
a00047879
Fig. 65: Complete configuration using the Promag 53 GSD file (complete device functionality)
It is essential to adhere to the following sequence when configuring the modules in the
PROFIBUS master (Class 1):
Slot
sequence
Module
Byte length
input data
Byte length
output data
Description
1AI 5-
Analog Input function block 1
Output variable volume flow (factory setting)
2 SETTOT_MODETOT_TOTAL 5 2
Totalizer function block 1
TOTAL output variable = volume flow (factory setting)
SETTOT totalizer control
MODETOT totalizer configuration
3 SETTOT_MODETOT_TOTAL 5 2
Totalizer function block 2
TOTAL output variable = volume flow (factory setting)
SETTOT totalizer control
MODETOT totalizer configuration
4 SETTOT_MODETOT_TOTAL 5 2
Totalizer function block 3
TOTAL output variable = volume flow (factory setting)
SETTOT totalizer control
MODETOT totalizer configuration
5AI 5-
Analog Input function block 2
Output variable mass flow (factory setting)
6 DISPLAY_VALUE - 5 Value for local display
7 CONTROL_BLOCK - 1 Control of device functions