Proline Prosonic Flow P 500 HART Commissioning
Endress+Hauser 111
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
interface / User
entry
Factory setting
Operating mode – Define the output as a pulse,
frequency or switch output.
• Pulse
• Frequency
• Switch
Pulse
Terminal number – Shows the terminal numbers
used by the PFS output
module.
• Not used
• 24-25 (I/O 2)
• 22-23 (I/O 3)
–
Signal mode – Select the signal mode for the
PFS output.
• Passive
• Active
*
• Passive NE
Passive
Assign pulse output The Pulse option is selected in
Operating mode parameter.
Select process variable for
pulse output.
• Off
• Volume flow
• Mass flow
• GSV flow
*
• NSV flow
*
• S&W volume flow
*
• Product 1 volume
flow
*
• Product 2 volume
flow
*
• Product 3 volume
flow
*
• Product 4 volume
flow
*
• Product 5 volume
flow
*
• Product 1 mass
flow
*
• Product 2 mass
flow
*
• Product 3 mass
flow
*
• Product 4 mass
flow
*
• Product 5 mass
flow
*
• Product 1 NSV
flow
*
• Product 2 NSV
flow
*
• Product 3 NSV
flow
*
• Product 4 NSV
flow
*
• Product 5 NSV
flow
*
Off
Pulse scaling The Pulse option is selected in
the Operating mode
parameter (→ 110) and a
process variable is selected in
the Assign pulse output
parameter (→ 111).
Enter quantity for measured
value at which a pulse is
output.
Positive floating
point number
Depends on country
and nominal
diameter
Pulse width The Pulse option is selected in
the Operating mode
parameter (→ 110) and a
process variable is selected in
the Assign pulse output
parameter (→ 111).
Define time width of the
output pulse.
0.05 to 2 000 ms 100 ms