Proline Prosonic Flow P 500 HART Technical data
Endress+Hauser 199
Maximum switching
capacity (passive)
DC 30 V, 0.1 A
AC 30 V, 0.5 A
Assignable functions Disable
On
Diagnostic behavior
Limit
Volume flow
Mass flow
Flow velocity
Electronics temperature
Sound velocity
Totalizer 1-3
Flow direction monitoring
Status
Low flow cut off
The range of options increases if the measuring device has one or more
application packages.
User-configurable input/output
One specific input or output is assigned to a user-configurable input/output (configurable
I/O) during device commissioning.
The following inputs and outputs are available for assignment:
Choice of current output: 4 to 20 mA (active), 0/4 to 20 mA (passive)
Pulse/frequency/switch output
Choice of current input: 4 to 20 mA (active), 0/4 to 20 mA (passive)
Status input
Signal on alarm Depending on the interface, failure information is displayed as follows:
Current output 0/4 to 20 mA
4 to 20 mA
Failure mode Choose from:
4 to 20 mA in accordance with NAMUR recommendation NE 43
4 to 20 mA in accordance with US
Min. value: 3.59 mA
Max. value: 22.5 mA
Definable value between: 3.59 to 22.5 mA
Actual value
Last valid value
0 to 20 mA
Failure mode Choose from:
Maximum alarm: 22 mA
Definable value between: 0 to 20.5 mA
Pulse/frequency/switch output
Pulse output
Fault mode Choose from:
Actual value
No pulses
Frequency output