EasyManua.ls Logo

Endress+Hauser Proline Prosonic Flow P 500 - Page 90

Endress+Hauser Proline Prosonic Flow P 500
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
System integration Proline Prosonic Flow P 500 HART
90 Endress+Hauser
Dynamic variables Measured variables
(HART device variables)
Primary dynamic variable (PV) Volume flow
Secondary dynamic variable (SV) Totalizer 1
Tertiary dynamic variable (TV) Totalizer 2
Quaternary dynamic variable (QV) Totalizer 3
The assignment of the measured variables to the dynamic variables can be modified and
assigned as desired via local operation and the operating tool using the following
parameters:
Expert → Communication → HART output → Output → Assign PV
Expert → Communication → HART output → Output → Assign SV
Expert → Communication → HART output → Output → Assign TV
Expert → Communication → HART output → Output → Assign QV
The following measured variables can be assigned to the dynamic variables:
Measured variables for PV (primary dynamic variable)
Measured variables which are generally available:
Volume flow
Mass flow
Flow velocity
Sound velocity
Electronics temperature
Additional measured variables with the Heartbeat Verification + Monitoring application
package:
Signal strength
Signal to noise ratio
Acceptance rate
Turbulence
Measured variables for SV, TV, QV (secondary, tertiary and quaternary dynamic
variable)
Measured variables which are always available:
Volume flow
Mass flow
Flow velocity
Sound velocity
Electronics temperature
Totalizer 1
Totalizer 2
Totalizer 3
HART input
Current input 1
5)
Current input 2
5)
Current input 3
5)
Additional measured variables with the Heartbeat Verification + Monitoring application
package:
Signal strength
Signal to noise ratio
Acceptance rate
Turbulence
5) Visible depending on the order options or device settings

Table of Contents

Other manuals for Endress+Hauser Proline Prosonic Flow P 500

Related product manuals