Commissioning Proline Prowirl R 200 HART
88 Endress+Hauser
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
Assign frequency output The Frequency option is
selected in the Operating
mode parameter (→ 85)
parameter.
Select process variable for
frequency output.
• Off
• Volume flow
• Corrected volume
flow
• Mass flow
• Flow velocity
• Temperature
• Pressure
• Calculated
saturated steam
pressure
*
• Total mass flow
*
• Energy flow
*
• Heat flow
difference
*
Off
Minimum frequency value In the Operating mode
parameter, the Frequency
option is selected, and one of
the following options is
selected in the Assign
frequency output parameter
(→ 88):
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Pressure
• Calculated saturated steam
pressure
*
• Total mass flow
*
• Energy flow
*
• Heat flow difference
*
Enter minimum frequency. 0 to 1 000 Hz 0 Hz
Maximum frequency value In the Operating mode
parameter, the Frequency
option is selected, and one of
the following options is
selected in the Assign
frequency output parameter
(→ 88):
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Pressure
• Calculated saturated steam
pressure
*
• Total mass flow
*
• Energy flow
*
• Heat flow difference
*
Enter maximum frequency. 0 to 1 000 Hz 1 000 Hz