156
General data
Safety equipment
Maximum efficiency 96.2 %
CEC efficiency at 208 V
at 240 V
at 277 V
95.0 %
95.5 %
96.0 %
Night consumption < 1.5 W
Consumption during operation 14 W
Cooling Controlled forced ventilation
Degree of protection NEMA 3R
Unit dimensions w x h x d 17.09 x 36.46 x 9.61 in.
434 x 926 x 244 mm
Power stage set weight 57 lbs.
26 kg
Connection area weight 26 lbs.
12 kg
Shipping dimensions w x h x d 20.28 x 42.72 x 14.02 in.
515 x 1085 x 356 mm
Shipping weight 90 lbs.
41 kg
Permissible ambient temperature
(with 95% rel. humidity)
-13 °F - +131 °F
- 25 °C - +55 °C
Permitted storage temperature
(with 95% rel. humidity)
-13 °F - +149 °F
- 25 °C - +65 °C
Ground fault protection internal GFDI
(Ground Fault Detector/Interrupter)
Islanding protection integrated
Protection against reverse polarity integrated
Arc detection / interruption integrated
Over temperature output power derating /
active cooling