58
1
IMPORTANT! Check the polarity and volta-
ge of the solar module strings: the voltage
should be a max. of 600 V, the difference
between the individual solar module strings
should be a max. of 10 V.
Inserting string
fuses
IMPORTANT The inverter is shipped with conductive slugs in the fuse holders. Series fus-
ing may be required depending on the type of solar module used in the system.
See NEC 690.9.
Select string fuses according to the information from the solar module manufacturer
or as per ‘Criteria for the proper selection of string fuses’ (max. 20 A per individual DC
terminal)
1
1
16
IMPORTANT!
- Follow all solar module safety instructions
- Follow all solar module manufacturer requirements
WARNING! An electric shock can be fatal. Danger from DC voltage from solar
modules. Fuse covers are for installation purposes only. They offer no protection
against contact.
1
1
4
2
3
DC-
DC-
2
NOTE!
- Insert fuses only with a fuse
cover in the respective fuse
holder
- Do not operate the inverter
without fuse covers

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fronius IG Plus A 3.0-1 UNI and is the answer not in the manual?

Fronius IG Plus A 3.0-1 UNI Specifications

General IconGeneral
AC nominal output3000 W
Max. apparent AC power3000 VA
Max. output current13 A
AC grid frequency50 / 60 Hz
THD<3%
Max. DC voltage500 V
Number of MPP trackers1
AC voltage range183 V - 264 V
DC input voltage range150 - 450 V
CoolingConvection