EasyManuals Logo

Fronius IG Plus A 3.0-1 UNI User Manual

Fronius IG Plus A 3.0-1 UNI
180 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
42
Polarity Reversal
of Solar Module
Strings
Connecting all solar module strings with reverse polarity will not cause any damage to the
inverter.
All solar module strings connected with reverse polari-
ty - no damage to the inverter
One single solar module string connected with reverse
polarity - risk of damage, risk of fire !
Overview ‘Connecting solar module strings to the inverter (DC)’ includes the following sections:
- Connecting solar module strings
- Criteria for the proper selection of string fuses
- Connecting combined solar module strings using connecting distributors
- Solar module ground at positive pole: Connecting solar module strings
- Criteria for the proper selection of string fuses
- Solar module ground at positive pole: Connecting combined solar module strings us-
ing connecting distributors
CAUTION! Risk of damage and fire to inverter due to reverse polarity of single
solar module strings.
Reverse polarity of even one single solar module string can cause an unaccept-
able thermal load, which can lead to an inverter fire.
Confirm string polarity and voltage before connecting DC wires to the inverter!
DC+ DC-
+
-
-
-
+
+
DC+ DC-
+
-
-
-
+
+

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fronius IG Plus A 3.0-1 UNI and is the answer not in the manual?

Fronius IG Plus A 3.0-1 UNI Specifications

General IconGeneral
AC nominal output3000 W
Max. apparent AC power3000 VA
Max. output current13 A
AC grid frequency50 / 60 Hz
THD<3%
Max. DC voltage500 V
Number of MPP trackers1
AC voltage range183 V - 264 V
DC input voltage range150 - 450 V
CoolingConvection