80
Illustration explanation: Data network with 3 Fronius IG Plus units and one Fronius Sensor
Box:
- all Fronius IG Plus units have one 'Fronius COM Card'
- one Fronius IG Plus has a 'Fronius Datalogger Card' (no. 2)
- Fronius Datalogger has a USB-interface and two RS-232 interfaces for connecting to
a PC and a modem
Option cards communicate within the Fronius IG Plus via its internal network. External
communication (Solar Net) takes place via the 'Fronius Com Cards.' Each 'Fronius Com
Card' is equipped with two RS422 interfaces - an input and an output. RJ45 plug connec-
tors are used to connect to these cards.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fronius IG Plus A 3.0-1 UNI and is the answer not in the manual?

Fronius IG Plus A 3.0-1 UNI Specifications

General IconGeneral
AC nominal output3000 W
Max. apparent AC power3000 VA
Max. output current13 A
AC grid frequency50 / 60 Hz
THD<3%
Max. DC voltage500 V
Number of MPP trackers1
AC voltage range183 V - 264 V
DC input voltage range150 - 450 V
CoolingConvection