Service and troubleshooting
EST3 Installation and Service Manual 8.31
Table 8-20: Local trouble pseudo points
Address Label Source Description
0689 Smoke Power Current Limit
Card 2
3-DSDC
3-SSDC1
3-SDDC1
Defective module
0690 Configuration Mismatch Slot 1 3-DSDC
3-SSDC1
3-SDDC1
N/A
Table 8-21: Local monitor pseudo points
Address Label Source Description
0615 Incoming Ring 3-MODCOM An incoming call was received by the
module.
0622 Outgoing Call in Progress Dialer is active
0650 All Call Active 3-ASU Changes to the active state when an
operator presses the All Call switch
0651 Mic Key Active 3-ASU Changes to the active state when an
operator presses the push-to-talk
switch on the paging microphone.
0673 Mapping In Progress Data
Card 1
3-DSDC
3-SSDC1
3-SDDC1
N/A
0674 Mapping Disbld Data Card 1 3-DSDC
3-SSDC1
3-SDDC1
Mapping manually disabled
0675 Device Maint Alert 3-AADC1 N/A
0675 Device Maint Alert Data Card
1
3-DSDC
3-SSDC1
3-SDDC1
Dirty detector on loop 1
0678 Reconstct Line Data Card 1 3-DSDC
3-SSDC1
3-SDDC1
N/A
0683 Mapping In Progress Data
Card 2
3-DSDC
3-SSDC1
3-SDDC1
N/A
0684 Mapping Disbld Data Card 2 3-DSDC
3-SSDC1
3-SDDC1
Mapping manually disabled
0685 Device Maint Alert Data Card
2
3-DSDC
3-SSDC1
3-SDDC1
Dirty detector on loop 2