Service and troubleshooting
8.32 EST3 Installation and Service Manual
Table 8-21: Local monitor pseudo points
Address Label Source Description
0688 Reconstct Line Data Card 2 3-DSDC
3-SSDC1
3-SDDC1
N/A
Table 8-22: Nonsupervised output pseudo points
Address Label Source Description
0621 Manual Answer Control 3-MODCOM Answers incoming call
Table 8-23: CRC pseudo points
Address Label Event type Description
SS01 AC Brownout Access trouble Sustained low voltage from CRC
supply to device
SS02 Low Battery Access trouble CRC battery below specified
voltage
SS03 Tamper Security alarm CRC tamper switch was
activated
SS04 Strike Fault Access trouble Strike device failed
SS05 Reader Fault Access trouble Card reader failed
SS06 RAM Fault or Stack Fault Access trouble CRC processor failed
SS07 Code Supervision Access trouble CRC executable program corrupt
SS08 Database Supervision Access trouble CRC database corrupt
SS09 Communications Fault Access trouble CRC lost communication with
3-SAC
SS10 Loop 1 Security alarm
(configurable)
Input device on loop 1 activated
SS11 Loop 2 Security alarm
(configurable)
Input device on loop 2 activated
SS12 Task Failure Local trouble Changes to the active state
when a task fails to execute
properly
SS15 Waiting for SDU Download Local trouble Database download from the
SDU is in progress or was
incomplete
SS32 CRC Strike Timed Access output Activate the strike device for a
specified interval
SS33 CRC Strike Unlock Access output Activate the strike device
SS34 CRC Relay Timed Access output Activate the CRC relay for a
specified interval