System overview
EST3 Installation and Service Manual 1.37
The All Call command directs the page signal to all areas of the
building, as illustrated in the last column of Figure 1-17.
Any combination of floors and stairwells could be selected to
receive the page by manually selecting the audio zones on the
audio zone select control/display module. Notice that at no time
does any area receiving a signal have its signal interrupted by
any page command function.
Evacuation (EVAC) channel
The EVAC channel always carries a signal designed to notify the
occupants they must leave the facility. The evacuation signal
may take the form of a textual message, a variety of audio tones,
or an audio tone modulated by the standard 3-3-3 evacuation
pattern, or any combination of these signals.
The EVAC channel is preprogrammed, and activated by the
system in response to an alarm. The EVAC signal is
automatically sent to the areas that are in danger and require
immediate evacuation.
The EVAC channel has priority over all channels signals except
for the Page channel. The alarm silence function automatically
silences the EVAC channel when an operator presses the Alarm
Silence switch.
Alert channel
The Alert channel always carries a signal designed to notify the
occupants that an emergency situation exists in the facility.
Occupants hearing the alert signal are not in immediate danger,
but should prepare to evacuate. In some installations, the alert
signal advises occupants that persons evacuating the danger area
will be entering the area for safety.
The Alert channel is preprogrammed, and activated by the
system in response to an alarm. The Alert signal is automatically
sent to areas that are not in immediate danger and do not require
immediate evacuation.
The Alert channel has priority over all other channels except the
Page and EVAC channels. The alarm silence function
automatically silences the Alert channel when an operator
presses the Alarm Silence switch.
General channel
The General channel is used to distribute special purpose signals
to special areas in the facility. Typically these areas include
elevator cabs, stairwells, and areas in less peril than those areas
receiving the Alert signal.
The general channel signals can be preprogrammed in response
to an alarm, or they may be manually activated.