4.  Ensure: 
•  The System state indicator LED OK (item 25 in Figure 3-7) is off. 
•  The NO contact of the fail alarm is open. 
•  The NC contact of the fail alarm is closed. 
•  If connected, the SCADA system has detected the alarm. 
7.2.4.4  Cancelling the Fail Alarm 
1.  Set the same parameter RelayMode to Normal. 
2.  Ensure: 
•  The System state indicator LED OK (item 25 in Figure 3-7) is lit. 
•  The NO contact of the fail alarm is closed. 
•  The NC contact of the fail alarm is open. 
•  If  connected,  the  SCADA  system  has  detected  the  state  change  of  the  fail 
alarm relay. 
7.2.4.5  Cancelling the Gas Alarms 
1.  Access the submenu Relays/Analog;GasH Relay. 
2.  Set this relay’s parameter RelayMode to Normal. 
3.  Access the submenu Relays/Analog;GasHH Relay. 
4.  Set this relay’s parameter RelayMode to Normal. 
5.  Ensure:  
•  The High alarm state LED H (item 27 in Figure 3-7) is off. 
•  The High-High alarm state LED HH (item 26 in Figure 3-7) is off. 
•  The System state indicator LED OK (item 25 in Figure 3-7) is lit.  
•  The NO contact of the High alarm is open. 
•  The NC contact of the High alarm is closed. 
•  The NO contact of the High-High alarm is open. 
•  The NC contact of the High-High alarm is closed. 
•  The NO contact of the fail alarm is closed. 
•  The NC contact of the fail alarm is open. 
•  If connected,  the SCADA system  has detected the  state  change of  both  gas 
alarm relays. 
7.2.4.6  Conclusion 
1.  If  necessary,  set  the  parameter  RelayMode  of  each  alarm  relay  to  their  initial 
mode. 
2.  When all three relays have been tested, push END. 
3.  To abort an operation if needed, push ESC.  
7.2.5  Verifying the Backup Battery 
1.  Access the top of the extended menu by pushing ENTER twice (History appears). 
Note:    Once  accessed,  the  extended  menu  times  out  after  30  minutes  of  keypad 
inactivity.