•  Flexible  rather  than  rigid  conduits  should  be  used  near  the  H201Ci-C  to  ease 
installation and servicing. 
•  Conduits,  or  cable  armors,  should  be  made  of  steel  to  shield  against  magnetic 
fields. 
The procedure is as follows: 
1.  Remove the rubber plugs from the required openings of the H201Ci-C enclosure.  
2.  For  each  cable  being  used,  install  a  standard,  watertight  conduit  fitting  (not 
supplied).    Up  to  eight  conduits  may  be  installed  (supervisory  links,  AC  power 
supply). 
3.  Mount a conduit to each fitting. 
4.  Ground  the  conduits  and/or  cable  shields  at  some  point.    Follow  the  company 
regulations meticulously.  
 
8.3.4  Installing the Supervisory Link Cables 
Note:    The  supervisory  link  cables  have  already  been  run  into  conduits  up  to  the 
Hydran  201Ci-C  if  the  installation  of  the  Hydran  201Ti’s  is  completed  (see  Section 
7.3.9). 
1.  If required, trim the excess length from the end of the supervisory link cables to 
be wired into the H201Ci-C.  
Note:    The  total  maximum  length  of  all  supervisory  link  cables  connected  to  one 
H201Ci-C is 1,200 m (4,000 ft). 
2.  Ensure the four wires of each cable have been labeled (for identification purposes) 
at both ends. 
3.  Connect  the  wires  and  shield  of  one  cable  to  one  of  the  four  H201Ci-C’s 
termination boards.  For wiring details, see Table D - 8 in Appendix D. 
Note:  The shield is grounded through a capacitor at the H201Ti end to protect against 
radiofrequency interference.  Shields must also be directly grounded at the H201Ci-C’s 
termination board. 
The  H201Ci-Cs  operation  may  be  affected  if  wires  are  not 
connected  correctly.    Be  careful  when  installing  and  inserting 
each wire.  Be sure to insert all strands in the terminal; strands 
that touch two terminals cause problems.  Strip each wire to a 
maximum of  8  mm  before  installing  it.    Do  not  leave  trims  of 
metallic strands inside the H201Ci-Cs enclosure