Although  the  H201  sensor  is  not  affected  by  the  temperature,  monitor  its 
temperature regularly. 
 
13.1.20  SensTemp HH 
•  Alarm type:  Fail alarm 
•  Non-abbreviated description : Sensor temperature High-High  
•  Priority:  Medium  
•  Parameter(s) involved:  
-  SensTemp HH; SysOK Relay; FaultTrig. submenu; Section 5.5.7 
-  STempAlr HH (alarm set point); Temperature submenu; Section 5.5.3 
-  TempoAlr Delay; Temperature submenu; S Section 5.5.3 
•  Alarm cause(s):  Temperature of the Hydran  201 sensor above the STempAlr 
HH alarm set point  
Exposing the H201 sensor to temperatures above the STempAlr 
HH alarm set point can damage the sensor.  
Proceed as follows: 
1.  The  oil  is  probably  too  hot  at  the  location  where  the  H201  sensor  is  installed; 
install the Hydran 201Ti at another location on the transformer tank, preferably at 
the bottom.  For details on typical installations, see Section 6.2.2.3. 
2.  If not already done, install the finned high temperature adaptor shown in Figure B 
- 6; it can be purchased from General Electric. 
 
13.1.21  SensTemp L 
•  Alarm type:  Fail alarm 
•  Non-abbreviated description:  Sensor temperature Low 
•  Priority:  Low 
•  Parameter(s) involved:  
-  SensTemp L; SysOK Relay;FaultTrig. submenu; Section 5.5.7 
-  STempAlr L (alarm set point); Temperature submenu; Section 5.5.3 
-  TempoAlr Delay; Temperature submenu; Section 5.5.3 
•  Alarm cause(s):  Temperature of the Hydran 201 sensor below the STempAlr L 
alarm set point  
Although  the  H201  sensor  is  not  affected  by  the  temperature,  monitor  its 
temperature regularly.