Hydran* 201i Instruction Manual 
 
MA-033  Rev. 14.0,  12-Nov-18 
 
14.8  Hydran 201Ci Controller Verification 
Frequency:  Annually or on fail alarm 
Note:  Alarms  are  triggered  during  this  verification  procedure.  Please  warn  the 
appropriate personnel. 
The H201Ci is verified as follows: 
1.  Check for water or dust infiltration inside the enclosure. 
2.  If necessary, clean and fix the enclosure. 
3.  Check for loose connections on the terminal blocks and connectors. Retighten if 
necessary.  
AC power supply voltage is present on most terminals. 
4.  Verify  the  LED’s,  the  heater  and  the  display  by  performing  the  procedure  in 
Section 9.2.2. 
5.  Verify the Hydran 201Ci-1’s analog output by performing the procedure in Section 
9.2.3. 
6.  If  the  H201Ci-1  is  not  currently  in  operation  and  if  its  alarm  contacts  are  used 
(connected  to  a  SCADA  system),  verify  the  alarm  indicators  and  relays  by 
performing the procedure in Section 9.2.4. 
7.  Verify  the  RS-232  or  USB  and  RS-485  communications  by  performing  the 
procedure in Section 8.2.3. 
 
14.9  Fuse 
The Hydran 201Ti, the Hydran 201Ci-C and the Hydran 201Ci-1 require the following 
type of fuse: 
•  5 A 
•  250 VAC 
•  5 x 20mm 
•  Slow blow / Time delay