13.1.7 DayTrend L 
•  Alarm type:  Fail alarm 
•  Non-abbreviated description:  Daily trend Low 
•  Priority:  Medium 
•  Parameter(s) involved:  
-  DayTrend L; SysOK Relay;FaultTrig. submenu; Section 5.5.7.  
-  DayTrAlr L (alarm set point); Gas;DailyTrend submenu; Section 5.5.2.3. 
-  DayTrAlr Delay; Gas;DailyTrend submenu; Section 5.5.2.3. 
 
•  Alarm  cause(s):    Daily  trend  below  the  DayTrAlr  L  alarm  set  point.  Probably 
indicates a gas level reading problem.  
 
Proceed as follows: 
1.  Verify the daily trend calculated by the Hydran 201Ti.  This value is displayed in 
the Main Display mode (see Section 5.2.2) and also in the DailyTrend screen in the 
Gas;DailyTrend submenu (see Section 5.5.2.3).  If this value seems normal, verify 
whether  the  value  of  the  alarm  set  point  is  adequate.    This  parameter  was 
probably set to a value that is too high. 
2.  Verify the gas level measured by the H201Ti.  This value is displayed in the Main 
Display  mode  (see  Section  5.2.2)  and  also  in  the  GasLevel  screen  in  the  Gas; 
GasLevel submenu (see Section 5.5.2.1). If this value seems normal, verify whether 
the value of the alarm set point is adequate.  This parameter was probably set to 
a value that is too high. 
3.  Verify  whether  the  breathing  membrane  of  the  H201Ti’s  enclosure  (item  4  in 
Figure  3-1)  and/or  the  one  of  the  Hydran  201  sensor  (see  Figure  3-3)  are 
obstructed by paint, grease or other products. 
4.  Verify whether the valve on which the H201Ti is installed is open. 
5.  Execute  the  ForceSensor  Test  command  in  the  Service  submenu  to  test  the 
operation  of  the  H201  sensor.    A  problem  may  have  occurred  since  the  last 
automatic  sensor  test  (which  is  performed  the  first  and  fifteenth  days  of  each 
month at midnight). 
 
13.1.8 DayTrend LL 
•  Alarm type:  Fail alarm 
•  Non-abbreviated description:  Daily trend Low-Low 
•  Priority:  Medium 
•  Parameter(s) involved:  
-  DayTrend LL; SysOK Relay;FaultTrig. submenu; Section 5.5.7. 
-  DayTrAlr LL (alarm set point); Gas;DailyTrend submenu; Section 5.5.2.3. 
-  DayTrAlr Delay; Gas;DailyTrend submenu; Section 5.5.2.3.