•  PowerStat. ID (identification number of the power station):  All H201Ti’s in the 
local  network  (power station)  must  be  set to  the  same  PowerStat.  ID  value.  
This number can vary from 1 to 9999. 
3.  To  continue  the  installation using  a  host  computer,  run  either  the  Hydran  Host 
software  (if  201Ti  is  set  to  Hydran  protocol)  or  Perception  software  (if  Hydran 
201Ti  is  set  to  Modbus  protocol)  to  define  a  local  network  using  these 
identification numbers.  See the Hydran Host Software Manual or Perception User 
Manual. 
 
7.4.11 Verifying and Setting the Operation Mode of the Alarm Relays 
For  details  on  the  parameters  and  commands  in  the  submenu  Relays/Analog,  see 
Section 5.5.7. For details on relays, see Section 11.2. 
1.  Access the submenu H201Ti Vx.xx; Relays/Analog. 
2.  Verify and set, as required, the three RelayMode parameters.  
 
7.4.12 Verifying and Setting the Fail Alarm Conditions 
1.  Access the submenu SysOK Relay; FaultTrig. 
2.  Verify  and  set,  as  required,  the  16  trigger  conditions  of  the  Hydran  201Ti’s  fail 
alarm relay. 
Note:  An asterisk at the end of the display’s bottom line indicates that the parameter is 
turned on (the fail alarm is triggered if this condition is detected).  A space indicates that 
the parameter is off. 
 
7.4.13 Verifying and Setting the Operation Mode of the Analog Output 
and TDM Signal 
1.  Access the submenu H201Ti Vx.xx; Relays/Analog. 
2.  Verify and set, as required, the parameters AnalogMode and TDM Mode.  
 
7.4.14 Conclusion 
If the  configuration has been  performed using  a  host computer connected  to the  USB 
connector located at the back of the CPU module, proceed as follows: 
1.  Access the submenu Communication. 
2.  Set the parameter CommChannel (communication channel) to Supervisory Link 
(for Hydran protocol) or SuprvLink MODBUS (for Modbus protocol). 
3.  Press END to return to the Main Display mode.  
 
The Hydran 201Ti configuration is now completed.