9.1.3  Storage 
If  the  Hydran  201Ci-1  is  not  installed  immediately,  it  is  strongly  recommended  to 
store it in its original shipping box in a safe place.  Ensure that the door-mounted push-
buttons are covered with the protective caps. 
Storage should be at a temperature between 5 and 45°C (41 and 113°F) and a non-
condensing,  relative  humidity  between  5  and  95%;  if  these  limits  are  to  be  exceeded, 
please contact the General Electric Customer Service (contact information can be found 
at the bottom of page 2). These restrictions do not apply to transportation. 
 
9.2  Verification of Operation Prior to Installation 
It  is  strongly  recommended  that  you  verify  the  operation  of  the  Hydran  201Ci-1 
Controller  before  installation  in  the  field.    The  verification  confirms  that  no  damage 
occurred during shipping and allows the user to become familiar with the H201Ci-1. 
 
9.2.1  Preparation 
To verify  its  operation,  the  Hydran 201Ci-1  must first  be  connected  to  a functional 
Hydran 201Ti via a supervisory link cable.  One end of this cable is already connected to 
the H201Ti.  For details on commissioning the H201Ti(s), see Chapter 7. 
Proceed as follows: 
 
1.  Connect  a  three-wire power cord to the AC Power 3-Terminal Block on the first 
H201Ti (item 8 in Figure 3-4):  The live side to L1/L, the other side to L2/N, and the 
ground to E/G.  For additional wiring details, see Table D - 1. 
2.  Connect the second end of the three-pair supervisory link cable coming out of the 
H201Ti to the main terminal block on the H201Ci-C (item 6 in Figure 4-6). 
3.  Power On the H201Ti. 
4.  Ensure the H201Ti is operating normally and no gas or fail alarms are present, by 
looking at the small  LED indicators on the  right side of the I/O module  (refer to 
Section 3.4.6.3). 
5.  Connect a power cord to the terminals 1 and 2 on the main terminal block of the 
H201Ci-1 (item 6 in Figure 4-6) and connect the E/G wire to the enclosure chassis. 
6.  Power On the H201Ci-1.