Hydran* 201i Instruction Manual 
 
MA-033  Rev. 14.0,  12-Nov-18 
 
The  Hydran  201i  System  gives  a  composite  reading  of  the  first  four  gases  in  the 
above  list,  in  other  words  the  gases  generated  by  transformer  incipient  faults.    This 
reading can be compared to the DGA results using the following formula: 
 
H201Ti reading = 100 % [H
2
] + 18 % [CO] + 8 % [C
2
H
2
] + 1.5 % [C
2
H
4
] 
 
A few examples are given in Table 14-2. The difference between the actual and the 
calculated  readings  should  fall  within  the  technical  specifications  of  the  Hydran  201i 
System. 
Dissolved Gas Analysis (DGA) (ppm) 
Table 14-2: Examples of Gas Reading Comparisons between a DGA and a Hydran 201Ti 
 
14.7  Hydran 201Ti Verification 
Frequency:  Annually or on fail alarm 
Note: Alarms are triggered during this verification procedure. Please warn the appropriate 
personnel. 
Read the  precautions listed  in Section  6.1  before  handling  the 
Hydran 201 sensor. 
The H201Ti is verified as follows: 
1.  Check for oil leaks.  
2.  If necessary, clean and retighten the brass adaptor and the H201 sensor.  
3.  Check for loose connections on the terminal blocks and connectors. Retighten if 
necessary.