Note: When the H201Ti is installed horizontally, the terminals must be facing up and
located under the sensor. Also, ensure that both the bleed screw and sampling port
remain easy to access.
2. Plug the twist-lock female connector of the sensor cable to the male connector
behind the Hydran 201 sensor,
Figure 7-8: Fastening the Heating Plate to the Brass Adapter
7.3.8 Installing the Cable Conduits
Note the following considerations prior to installing:
• All cables connected to the Hydran 201Ti must be run through steel conduits
in accordance with local wiring regulations. Otherwise, armored cables can be
used.
• Flexible rather than rigid conduits should be used near the H201Ti to ease
installation and servicing.